HCVR-3

The HCVR-3 is a 3 zone conventional releasing fire alarm control panel that is UL Listed and FM Approved for releasing.

The HCVR-3 can be configured to activate releasing by a single zone or combination of any two zones. The LCD display is used to show the countdown timer during activation of the releasing sequence.

The HCVR-3 is fully programmable using simple menu options. The panel is a single board construction which provides an easy replacement solution. It is also compatible with a wide range of devices.

STANDARD FEATURES

  • UL 864 Listed and FM Approved
  • Three detection zones
  • Any single zone or any combination of zones can be configured to release
  • Fully programmable using simple menu options
  • Simple, single board construction
  • Installer friendly
  • Compatible with wide range of detection devices
  • Configurable first stage NAC delays
  • Configurable detection delays
  • Built-in Manual Release switch and separate circuit
  • Compatible with FirePro Xtinguish™
  • Compatible with various releasing valves
  • Configurable releasing delays up to 60 seconds in 5 second intervals
  • Configurable releasing duration up to 5 minutes in 5 second intervals
  • Releasing countdown timer displayed on the LCD
  • Supports up to seven HCVR-SDU or HCVR-AB
  • Built-in relays for Fire, Trouble, Stage 1, Stage 2, Extract and Local Fire.

 

The HCVR-3 is a 3 zone conventional releasing fire alarm control panel that is UL Listed and FM Approved for releasing.

Informasi Tambahan

Supply Voltage

115VAC (50hz/60hz) or 230VAC (50hz/60hz)

Power Supply DC Rating

24V 3 Amps

Mains Supply Fuse

1.6 Amps 250V

Dimension

14.5" (W) x 12.2" (H) x 3.5" (D)

Weight

12.3 lbs. w/o batteries

Color

Red

Material

1.2mm mild steel

Max. Battery Size

7Ah 12V (2 per panel)

RS-485 Serial Bus

Maximum line impedance 120 Ohms

Trouble Contact Rating

30VDC 1 Amp

Local Fire Contact Rating

30VDC 1 Amp

Fire Contact Rating

30VDC 1 Amp

1st Stage Contact Rating

30VDC 1 Amp

2nd Stage Contact Rating

30VDC 1 Amp

EXTRACT Output

30VDC 1 Amp contacts for (NO) and (C)

EXISTING Output Rating

18 to 28VDC 1 Amp max load for 5 minutes and voltage reversing DC

NAC Output Rating

0.5 Amp per output

Detection Zone End of line resistor

6K8 Ohms 5% resistor

NAC Output

10K Ohms 5% resistor

Stand by Current

86 mA

Alarm Current

620 mA

Operating Humidity

95% RH Non-Condensing

Operating Temperature

-5°C to +40°C (23°F to 104°F)