The HCVR-3 is a 3 zone conventional releasing fire alarm control panel that is UL Listed and FM Approved for releasing.
HCVR-3
The HCVR-3 is a 3 zone conventional releasing fire alarm control panel that is UL Listed and FM Approved for releasing.
The HCVR-3 can be configured to activate releasing by a single zone or combination of any two zones. The LCD display is used to show the countdown timer during activation of the releasing sequence.
The HCVR-3 is fully programmable using simple menu options. The panel is a single board construction which provides an easy replacement solution. It is also compatible with a wide range of devices.
STANDARD FEATURES
- UL 864 Listed and FM Approved
- Three detection zones
- Any single zone or any combination of zones can be configured to release
- Fully programmable using simple menu options
- Simple, single board construction
- Installer friendly
- Compatible with wide range of detection devices
- Configurable first stage NAC delays
- Configurable detection delays
- Built-in Manual Release switch and separate circuit
- Compatible with FirePro Xtinguish™
- Compatible with various releasing valves
- Configurable releasing delays up to 60 seconds in 5 second intervals
- Configurable releasing duration up to 5 minutes in 5 second intervals
- Releasing countdown timer displayed on the LCD
- Supports up to seven HCVR-SDU or HCVR-AB
- Built-in relays for Fire, Trouble, Stage 1, Stage 2, Extract and Local Fire.

Informasi Tambahan
| Supply Voltage | 115VAC (50hz/60hz) or 230VAC (50hz/60hz) |
|---|---|
| Power Supply DC Rating | 24V 3 Amps |
| Mains Supply Fuse | 1.6 Amps 250V |
| Dimension | 14.5" (W) x 12.2" (H) x 3.5" (D) |
| Weight | 12.3 lbs. w/o batteries |
| Color | Red |
| Material | 1.2mm mild steel |
| Max. Battery Size | 7Ah 12V (2 per panel) |
| RS-485 Serial Bus | Maximum line impedance 120 Ohms |
| Trouble Contact Rating | 30VDC 1 Amp |
| Local Fire Contact Rating | 30VDC 1 Amp |
| Fire Contact Rating | 30VDC 1 Amp |
| 1st Stage Contact Rating | 30VDC 1 Amp |
| 2nd Stage Contact Rating | 30VDC 1 Amp |
| EXTRACT Output | 30VDC 1 Amp contacts for (NO) and (C) |
| EXISTING Output Rating | 18 to 28VDC 1 Amp max load for 5 minutes and voltage reversing DC |
| NAC Output Rating | 0.5 Amp per output |
| Detection Zone End of line resistor | 6K8 Ohms 5% resistor |
| NAC Output | 10K Ohms 5% resistor |
| Stand by Current | 86 mA |
| Alarm Current | 620 mA |
| Operating Humidity | 95% RH Non-Condensing |
| Operating Temperature | -5°C to +40°C (23°F to 104°F) |