The HCV Series is available in a 2, 4, 8 Zone conventional panel design which is in accordance with BS EN54-2 and BS EN54-4 Detection and Fire Alarm Systems - Control and Indicating Equipment.
HCV EN Series
The HCV series is available in a 2, 4, 8 Zone conventional panel design which is in accordance with BS EN54-2 and BS EN54-4 Detection and Fire Alarm Systems – Control and Indi- cating Equipment.
The HCV series has an integrated Power Supply and Battery charging circuit. The control panel has “Voltage Free” Con- tacts for Fire and Local Fire which operate upon a fire condi- tion. These are used for local control and signaling. In accord- ance with BS EN54-4.
The HCV series are fully programmable using simple menu options. The Panel is a single board construction, which is installer friendly. Compatible with a wide range of detection devices. Remote control input terminals for Silence Alarm, Sound Alarm, Trouble and Reset
STANDARD FEATURES
-
- Fully compliant with & tested to BS EN54-2 and BS EN54-4
- 2-wire Annunciator
- Fully programmable using simple menu options
- Simple, single board construction
- Installer friendly
- Compatible with wide range of detection devices
- Two monitored Sounder outputs
- 3 Amp power supply
- Auxiliary power output
- Adjustable Sounder delay time
- Sounder configuration options
- Zonal Sounder delay detectors only
- Zonal Sounder delay call points only
- Coincidence input selection
- S. Barrier selection by zone
- Short circuit fire by zone
- Non latching zones
- Silent zones
- Available Model
– HCV-2/230V
– HCV-4/230V
– HCV-3/230V

Informasi Tambahan
| Supply Voltage | 120 VAC (50hz/60hz) or 230 VAC (50hz/60hz) |
|---|---|
| Power Supply DC Rating | 24V 3 Amps |
| Mains Supply Fuse | 1.6 Amps 250V |
| Dimension | 385mm (W) x 310mm (H) x 92mm (D) |
| Weight | 11.5 lbs. |
| Color | Red |
| Material | 1.2mm mild steel |
| Max. Battery Size | 7 Ah 12V (2 per panel) |
| Fault Contact Rating | 30VDC 1 Amp |
| Local Fire Contact Rating | 30VDC 1 Amp |
| Fire Contact Rating | 30VDC 1 Amp |
| NAC Output Rating | 0.5A per output (max 1.6A over all outputs) |
| Detection Zone Current | 1.6m Amps |
| End of line resistor Detection Zone | 6K8 Ohms 5% Resistor |
| End of line resistor Sounder Output | 10K Ohms 5% Resistor |
| Stand by Current | HCV-2: 0.065Amp, HCV-4: 0.075Amp, HCV-8: 0.093Amp |
| Alarm Current | HCV-2: 0.1Amp, HCV-4: 0.21Amp, HCV-8: 0.55Amp |
| Cable Capacity | 2.5mm per terminal |
| Operating Humidity | 95% RH (non condensing) |
| Operating Temperature | -5°C to +40°C |