The FireNET Plus® 1127 series control panel is a digitized analog addressable fire alarm panel with build options containing 1 or 2 SLC loops, an RS-485 bus for network communication and cellular dialer communica- tion options. Each SLC loop supports 127 devices of any combination (sensors or modules), and 127 analog sounder bases, for a possible total of 254 points per loop. Communication between devices is accomplished by use of standard cable (shielded or twisted pair is not required). Each panel includes a 4-amp power sup-ply and has 2 onboard NAC circuits. The RS-485 bus provides communication to the panel network while an- other RS-485 bus provides communication for peripher- al devices. The RS-232 interface allows the conven- ience of programming via a PC.
The system will support a variety of Hochiki devices such as photo, ion and heat sensors, which contain a unique, patented sensor design incorporating automatic drift compensation and day/night sensitivity modes. Additional devices include contact monitors, relay con- trollers, supervised auxiliary output and short circuit isolator modules. In addition, interfaces to conventional detection systems can be established by using a con- ventional zone-monitoring module.
The Loop Explorer Windows® Software interface pro- vides the installer with fingertip access to installation programming and diagnostic tools. An Auto Learn fea- ture offers the convenience for quick start applications. Add to this Hochiki’s reputation for high quality and dedicated service, and you have an exceptional product with performance and value.
STANDARD FEATURES
- Digitized analog information processed using Hochiki’s advanced Digital Communication Protocol for fast and robust communication
- Up to 127 sensors & modules, plus 127 analog sounder bases, for a total of 254 points possible per loop
- Uses standard wire, no-shielded or twisted pair required on SLC loops
- Optional dedicated cellular communicators, Pathway Pro and FireNET Comm 5G use serial data to transmit events.
- Programmable sensitivity levels by device
- Alarm verification feature
- Automatic daily calibration & drift compensation routine
- Large 8-line x 40-character LCD (320 char.)
- 1 SLC (2nd SLC optional)
- RS-485 bus for panel networking (option)
- Built-in RS-232 interface for programming via a PC
- 3 on board programmable Form C relays rated at 1 amp at 30VDC
- 2 auxiliary power outputs, each rated 360mA at 24 VDC
- Loop Explorer Windows® configuration utility
- Auto-learn feature
- 500 network wide software zones
- Network capability of up to 64 panels (option) except non expandable model
- Built in help and alarm information screens
- 2 on-board Class B (style Y) NAC circuits rated at 2.3 amps each (special application) and 1.6 amps each (regulated continuous)
- Gentex, System Sensor, Wheelock, and, Amseco NAC sync protocol built-in
- Automatic day/night sensitivity modes
- Fire Drill test function
- Walk test function
- Powerful & versatile programming software includes three types of Cause & Effect programming: Action, Disablement and Test.
- Seismic certified

Ulasan